"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Cond. Strands","Cond. Number","Diameter Over Conductor","Insulation Thickness","Ground","Diameter Over Armor","Jacket Thickness","Approx. OD","Aluminum Weight","Approx. Weight" "","AWG/Kcmil","No.","","inches","mils","No. x AWG","inches","mils","inches","lbs./MFT","lbs./MFT" "TBA","8","7","4","0.134","45","1 x 8","0.754","50","0.854","162","295" "TBA","6","7","4","0.169","45","1 x 8","0.839","50","0.939","213","364" "TBA","1/0","19","4","0.336","55","1 x 4","1.291","50","1.391","609","883" "TBA","2/0","19","4","0.376","55","1 x 4","1.388","50","1.488","727","1024" "TBA","3/0","19","4","0.422","55","1 x 4","1.599","60","1.719","877","1246" "TBA","4/0","19","4","0.474","55","1 x 2","1.725","60","1.845","1119","1521" "644656","250","22","4","0.52","65","1 x 2","1.887","65","2.019","1318","1869" "644652","350","35","4","0.615","65","1 x 2","2.118","65","2.250","1784","2432" "644649","500","35","4","0.735","65","1 x 2/0","2.408","80","2.574","2403","3232" "TBA","600","61","4","0.812","80","1 x 1","2.664","75","2.814","2922","3795" "640988","750","58","4","0.908","80","1 x 1/0","2.896","80","3.062","3409","4356" "Table 2 - Electrical and Engineering Data" "" "Stock Number","Cond. Size","Cond. Number","Min Bending Radius","Max Pull Tension","DC Resistance @ 25C","AC Resistance @ 90C","Inductive Reactance @ 60Hz","Allowable Ampacity At 75C","Allowable Ampacity At 90C" "","AWG/Kcmil","","inches","lb","ohm/MFT","ohm/MFT","ohm/1000ft","Amps","Amps" "TBA","8","4","6.0","316","1.072","1.290","0.052","32","36" "TBA","6","4","6.6","503","0.674","0.812","0.051","40","44" "TBA","1/0","4","9.7","2027","0.168","0.201","0.044","96","108" "TBA","2/0","4","10.4","2555","0.133","0.160","0.043","108","120" "TBA","3/0","4","12.0","3221","0.105","0.126","0.042","124","140" "TBA","4/0","4","12.9","4062","0.084","0.100","0.041","144","164" "644656","250","4","14.1","4800","0.071","0.086","0.041","164","184" "644652","350","4","15.8","6720","0.050","0.062","0.040","200","224" "644649","500","4","18.0","9600","0.035","0.044","0.039","248","280" "TBA","600","4","19.7","11520","0.029","0.037","0.039","272","308" "640988","750","4","21.4","14400","0.024","0.031","0.038","308","348" "All dimensions are nominal and subject to normal manufacturing tolerances"